ANR-897 TUNNEL VENTILATION IN POULTRY HOUSING
ANR-897, Revised Nov 1995. James
O. Donald, Extension Agricultural
Engineer, Professor, Agricultural Engineering
| Tunnel Ventilation in Poultry
Housing |
What Is Tunnel Ventilation?
Tunnel ventilation gets its name because in
this type of system the poultry house is converted into something
like a wind tunnel. In a tunnel ventilation system, all exhaust
fans are placed at one end of the house and all air inlets at
the other end. Ventilating air is drawn uniformly through the
length of the house at a velocity of at least 350 to 400 feet
per minute (4 to 4.5 mph). This high-velocity airflow through
the house provides significant cooling for the birds. Evaporative
cooling can provide additional protection against birds' overheating.
Tunnel ventilation is a warm-weather system.
Introducing all ventilating air at one end of the house can cause
chill stress on birds in cold weather. During hot weather, larger
birds conditioned to tunnel house temperatures will suffer heat
stress if power fails even if the house is immediately opened
up. For this reason, a back-up generator is essential.
Tunnel houses are usually designed to operate
at static pressures ranging from 0.06 to 0.10 inches. Houses using
curtain-wall or sidewall exhaust fan systems can be adapted to
tunnel ventilation. As in other negative-pressure ventilating
systems, a tight house with no air leaks is needed for successful
operation.
Benefits Of Tunnel Ventilation
Tunnel ventilation with evaporative cooling
can enable a grower to provide close to optimum conditions for
bird performance in hot weather. Managed properly, tunnel ventilation
not only prevents mortalities from heat but keeps birds feeding
and growing at a good rate. Also, growers have found that tunnel
ventilation allows them to maintain wintertime stocking rates
throughout the year rather than reducing bird density during the
hot months. The result can be higher net returns to the grower,
compared with other summer ventilation systems. The hotter the
weather, the better the payoff from tunnel ventilation is likely
to be.
Lowering Effective Air Temperature
Air velocity in a tunnel-ventilated house is
high enough to create a wind-chill effect on the birds, so that
they feel an "effective temperature" lower than the
actual outside air temperature. For example, if air at 90 degree
F is moved over the birds at 350 feet per minute, it feels to
the birds like about 75 degree F air.
Figure 1 shows the effective temperature experienced
by birds for different air velocities when outside air temperature
is 90 degree F. The wind-chill effect becomes less pronounced
as temperatures rise toward 100 degree F. When air temperature
is the same as or higher than the birds' internal body temperature
(slightly above 100 degree F), the air begins to warm the birds
instead of cooling them. Under these conditions, evaporative cooling
to lower the actual air temperature is needed to prevent heat
stress.
 |
Figure 1. Effective temperature
for broilers created by different air velocities when actual
air temperature is 90 degree F. |
Sizing And Locating Air Inlets And Fans
All air inlets and fans are placed in the building
endwalls and/or in the sidewalls next to the endwalls. If sidewall
installation is used, the arrangement should be balanced, with
fans or inlets in both sidewalls, not just in one side. Figure
2 shows a typical tunnel ventilation system.
 |
Figure 2. Fan and inlet arrangement
for a typical tunnel ventilation system. Cooling air sweeps through
the house at a high, uniform velocity. |
The house design should aim for an air velocity
of 400 feet per minute or more, exchanging house air about once
every minute. To find the total fan capacity needed, simply multiply
the air velocity wanted times the cross-sectional area of the
house. For example, in a house 40 feet wide by 400 feet long,
if ceiling height is 8 feet, cross-sectional area will be 320
square feet (8 feet * 40 feet) and the fan capacity required for
400 feet per minute air velocity will be:
400 ft./min. * 320 sq. ft. = 128,000
cfm.
Houses of this size typically use six to eight
48-inch fans to get this total fan capacity. The total house volume
will be 128,000 cubic feet (8 feet * 40 feet * 400 feet), so house
air will be exchanged about once every minute.
Total inlet area should be large enough to
insure smooth and uniform airflow through the house at about 400
feet per minute. If the inlet area is too small, air velocity
at the inlet end will be too high. When fans alone are used, the
total inlet area should be as close to the house cross-sectional
area as possible, consistent with maintaining static pressure.
Additional inlet area is needed when evaporative cooling is used,
as explained below under Cooling With Evaporative Pads.
If needed, the house cross-sectional area can
be effectively reduced by hanging deflector curtains from the
ceiling across the width of the house. This is especially helpful
in open ceiling houses. The deflectors are usually made of curtain
material and should be spaced not less than 40 feet apart down
the length of the house.
Selecting Fans
Ventilating fans must be designed to move air
against pressure in order to perform as expected. The design static
pressure, air inlet area, cooling pads, fan enclosures, shutters,
and guards all affect the amount of air that will be moved through
the house. Shutters alone can reduce fan capacity by 10 to 25
percent, compared with free air delivery. Choosing fans can be
difficult because manufacturer rating systems vary and may not
include testing with shutters and guards in place. Fans are often
rated at free air delivery and at 1/8-inch (0.125 in) static pressure.
Most fans on the market today have been tested
by the Air Movement and Control Association (AMCA). A testing
program at the University of Illinois rates commercially available
fans at various static pressures with shutters and guards in place
and in addition provides energy efficiency ratings. For a copy
of the test booklet, send a check for $5 payable to University
of Illinois to Steve Ford, 1304 W. Pennsylvania, Agricultural
Engineering Sciences Building, Urbana, IL 61801.
Using Evaporative Cooling
The combination of tunnel ventilation and evaporative
cooling can be very effective in reducing hot-weather heat stress.
Evaporating or vaporizing water lowers the air temperature and
raises the relative humidity of the air. If outside air relative
humidity is below 75 percent, evaporative cooling can almost always
bring air temperature down at least into the 80 degrees to 85
degrees F range. The lower the outside relative humidity, the
more cooling can be expected.
Generally, evaporative cooling should be started
when outside air temperature hits 85 degrees F but only if relative
humidity is below 75 percent. At higher relative humidity, wetting
of birds and litter is more likely, and cooling effect is limited.
Care should be exercised to avoid wetting of birds or litter.
Tunnel-ventilated poultry houses can use evaporative
pads, foggers, or misters for cooling. Fan and pad systems, along
with very high-pressure, low-volume fogging systems, can come
close to providing an optimum growth environment for the birds.
Cooling With Evaporative Pads. In a fan and pad system, outside air is cooled as
it is drawn through wetted pads usually placed outside the air
inlets. An advantage of external cooling pads is that water which
is not vaporized drips off the pad outside the house and not onto
the house floor. Fogging lines are often used to wet the pads.
Placing the pads across the air inlets restricts the inlets, so
total inlet area must be larger when evaporative pads are used.
For example, a typical recommendation might be 72 square feet
of pad area for each 48-inch fan. The type and thickness of pad
used, inlet area, and fan capacity must be matched to maintain
the air velocity and ventilating capacity (cubic feet per minute)
needed. Some pad systems add several fogging lines inside the
house to smooth out temperature variations as air moves through
the house.
Cooling With Fans And Foggers. When foggers or misters are used in a tunnel house,
they are spaced through the building so that cooling is distributed
throughout the house. High-pressure, low-volume foggers, operating
at 200 psi or more and with a flow rate of 1 gallon per hour or
less, are more efficient and carry less risk of wetting the birds
or the litter. This is because they produce smaller droplets of
water, which are more likely to be kept aloft in the air stream
long enough to evaporate.
Low-pressure, high-volume systems are much
less expensive and can help reduce mortalities but produce less
cooling effect and have to be monitored more closely to avoid
wetting down the house.
Controlling Bird Migration
In a tunnel house, birds tend to migrate toward
the air inlet end of the building. Crowding as a result can reduce
bird performance markedly. To control migration, fences should
be put up at least every 100 feet. These can be made from 2-inch
by 4-inch welded wire connected to a PVC framework about 18 inches
high.
Several factors contribute to migration, including
a natural tendency for birds to face into a wind so that when
they move they walk in that direction. However, in hot weather
birds will also tend to move toward a cooler area. If the inlet
air velocity is considerably higher than the velocity reached
after the air has spread in the house, the birds may be moving
toward this higher velocity and more cooling air. Also, the air
at the inlet end will naturally be a few degrees cooler. Since
the air moving through the house is picking up heat from the birds,
the air will warm several degrees by the time it reaches the fans.
Bird migration within fenced areas may occur
naturally, but if this crowding is pronounced it may signal inadequate
airflow, which causes large temperature differences. Usually inadequate
airflow results either from inadequate fan capacity, which may
be caused simply by dust build-up on fan blades and shutters,
or from air leaks in the ceiling or walls.
Tips On Operating A Tunnel House
- A tunnel ventilation system is designed to
cope with high summertime temperatures. In milder weather, the
system can be operated at less than capacity, that is, with fewer
fans running. However, if it is too cool to tunnel ventilate
with at least half the fans running, sidewall inlets or curtain
ventilation should be used. Moving the air too slowly through
the house risks allowing temperature, carbon dioxide, ammonia,
and humidity to rise to dangerous levels before the air gets
to the fan end.
- Fan thermostats can be set to bring fans
on in stages. Thermostat settings will depend on bird age. The
younger the bird, the fewer the feathers, the more easily heat
is removed from the bird. For fully feathered birds, the system
normally should be set to run at full capacity by the time the
air temperature reaches 80 degrees F.
- Evaporative cooling thermostats should be
set to start cooling at 80 degrees to 85 degrees F. Staging can
include switching fogging lines on in succession and switching
from low to high pressure settings. Evaporative cooling should
never be used at night or before 10 a.m. because the humidity
will be too high.
- Use an air velocity meter to monitor actual
airflow in the house. What counts is air velocity at bird level,
which usually will be slightly lower than air velocity at chest
height.
Appreciation is extended to L. Bynum Driggers,
former Extension Specialist, North Carolina State University,
for his permission to use some of the material in this publication. For
more information, contact your county Extension office. Look
in your telephone directory under your county's name to find the
number.
For more information, contact your county Extension office. Visit http://www.aces.edu/counties or look in your telephone directory under your county's name to find contact information.
Published by the Alabama Cooperative Extension System (Alabama A&M
University and Auburn University), an equal opportunity educator and
employer.
|
If you have problems loading
this document, please email publications@aces.edu
for assistance.
Publications Homepage | ACES Homepage
|